==Planning and Design==
 
==Planning and Design==
 
This section provides design guidance for laboratory location, location of staff and pre-analytical areas, sizing and location of laboratory furniture, sizing and location of storage areas, and designing current laboratories for future     
 
This section provides design guidance for laboratory location, location of staff and pre-analytical areas, sizing and location of laboratory furniture, sizing and location of storage areas, and designing current laboratories for future     
{| class="wikitable"
+
The laboratory design objective is primarily to develop environments in which laboratory activities can be conducted without compromise to laboratory processes, patient dignity and occupational health and safety.
|The laboratory design objective is primarily to develop   environments in which laboratory activities can be conducted without   compromise to laboratory processes, patient dignity and occupational health   and safety.
 
|}
 
 
 needs.
 
 needs.
  

Revision as of 13:12, 25 June 2020

Planning and Design

This section provides design guidance for laboratory location, location of staff and pre-analytical areas, sizing and location of laboratory furniture, sizing and location of storage areas, and designing current laboratories for future

The laboratory design objective is primarily to develop environments in which laboratory activities can be conducted without compromise to laboratory processes, patient dignity and occupational health and safety.

 needs.

Spatial Planning

This guidance document is written within an environment of rapidly developing and expanding point-of-care diagnostic techniques and technologies. In this environment much of the laboratory procedures is moving out of the laboratory and to the patient’s bedside. The impact on the laboratory is an emerging requirement for additional storage space and for more open and flexible laboratories. For this reason the development and planning of any laboratory cannot be undertaken without an informed understanding of the techniques and technologies that will be employed in that laboratory. Where this guidance document refers to separate clinical activities, it should be assumed that these functions, unless otherwise specified or due to or technical restrictions, may be conducted within one open plan area at the discretion of the service provider.

Space Adjacency Diagram


The questions to be asked and answered during the space planning stage of design relate to the adjacency of the required spaces and their inter-relationships.

An overall adjacency matrix is presented to facilitate this planning of these spaces. This matrix should be read in the context of the services that will be provided by the laboratory being planned. It will be seldom that all the spaces or function specified will be required in a single facility.

The space adjacency matrix presented is adapted from Guidelines for Laboratory Design: Health, Safety, and Environmental Considerations [1]

Interrelation Diagram

From the adjacency matrix, a space planning inter-relational diagram such as one depicted in Lab Space Adjacency Diagram. is developed. This diagram subsequently informs the development of the facility layouts. The example given indicated the flow of samples in the facility. Similarly the flow of staff and patients should also be described on such a diagram. This planning step is useful to ensure the relationships between processes and spaces are well understood and accommodated in this highly technical and variable environment. Waste storage and treatment areas are not shown in the example given.

The basic laboratory facility within a hospital or healthcare facility may accommodate one or more of the following clinical diagnostic activities:

1.       Clinical Pathology, which may include:

·        Haematology

·        Chemistry

·        Microbiology

·        Immunology

2.       Anatomical pathology, which may include:

·         Histology

·        Cytology

When planning the location of a laboratory within the hospital, the following factors should be considered and addressed:

·        The location should not be utilised as an escape route by patients or staff from other hospital department wards.

·        Laboratories should be located such that they cannot be used as thoroughfares for hospital staff or the general public.

·        Laboratories are considered to be sources of infection and fire hazard areas and therefore should not be located in areas frequented by the public.

·        Laboratories should not form part of general emergency egress routes. However, emergency egress routes should be planned from laboratories without compromising contaminations control and security requirements.

·        Facilities should be designed to comply with the National Building Regulations as amended.

Facility sizing

The following matrix offers guideline space planning for concept development benchmarking and high level costing of laboratory facilities.


SPACE PER HOSPITAL (m²)
Laboratory Areas 0-200 Beds 200-400 Beds 400-800 Beds
Community
Staff
Administrative
Pre-analytical
Analytical
Storage
Waste and Technical [TVR@1]


Functional areas

The functional areas in a laboratory can be described as, community areas, staff areas, pre-analytical areas, analytical areas and waste storage and treatment areas.

Staff Areas

1.       Staff facilities should include:

·        Protective clothing storage. This is normally in the form of individual lockers. Individual lockers give staff place to store street garments and valuables as required.

·        A tea room for resting, socialising and storage and preparation of beverages.

·        Education and training facilities – These are sometimes provided at central or tertiary facilities.

2.       Where full garment changing is required separate changing facilities should be provide for both male and female. Where lab practice deems it acceptable to wear lab coats over street clothes, dedicated change rooms may not be required.

3.       The staff compliment size determines the number of changing spaces and lockers. This consideration should include capacity for researchers and trainees where required by the service level agreement.

4.       Separate male, female and accessible toilets should be provided.

Pre-analytical areas

1.       Pre analytical areas include spaces for administrative and logistic operations. This includes spaces for sample receipt, storage and dispatch.

2.       Administrative offices should are used multiple people simultaneously for desk-based work. Administrative workspaces should be large enough to accommodate daily filing, stationary and a workstation.

3.       Each laboratory facility should have only one specimen reception area. This area should receive samples, capture and process test request and distribute the samples to the appropriate laboratory.

4.       Specimen sorting may be required. For this operation, a specimen sorting area is required immediately adjacent to the specimen receipt area, prior to dispatch to the relevant laboratory.

4.1.     The sorting area requires a number of individual work-stations for processing and packing of discrete sample batches to prevent mix-ups.

4.2.     Each work area should have adequate lighting and a space for a PC workstation to complete any electronic record workflow tasks.

4.3.     Hand wash facilities are required in all areas where specimen handling occurs.

5.       A room should be provided for the collection of primary samples. This area should be designed considering patient comfort, privacy (including acoustic privacy) and dignity without compromising the requirements of efficient sample collection. These areas should also be designed to accommodate the accessibility needs of persons with disabilities.

Analytical areas

1.       General Requirements

1.1.     The analytical areas for functional clinical laboratories include chemistry, haematology, pathology and cytology laboratories. This document is limited to the requirements of laboratories classified up to biosafety level 2. The range of services offered in a clinical laboratory varies from facility of facility and is dependent of the local service level agreement in place.

1.2.     The laboratory design objective is primarily to develop environments in which laboratory activities can be conducted without compromise to laboratory processes, quality and occupational health and safety. Sources of risk and recognised harm should be identified and mitigated against.

1.3.     A consultative workflow analysis is required at early conceptual design stage in order to resolve the following:

1.3.1.  Identification of incompatible processes or activities which need to be separated spatially and physically such that they require individual areas. Cross contamination between processes should be prevented.

1.3.2.  Modern clinical laboratory workflow and equipment does not require physical separation of activities into separate areas and an open-plan laboratory is acceptable except for the following:

1.3.3.  TB culture and diagnostics

1.3.4.  Microbiological Laboratory

1.3.5.  Cell culture laboratory

1.4.     Each laboratory module must be equipped with a wash-hand basin. See further for details.

1.5.     Sufficient space should be provided for automatic lab equipment. This equipment often requires access right around and has a continuous linear arrangement. Power, water and gas services to this equipment should be provided from overhead installations.

1.6.     Laboratory isles should not be narrower than 700mm with main isles no narrower than 1050mm. Main aisles used for emergency egress must comply with requirements of the National Building Regulations. Access for equipment movement and replacement should also be considered. Emergency exit routes should be clear of furniture and equipment.

1.7.     Door openings should not be less than 900mm. Refer below for further details.

1.8.     Biosafety cabinets should not be placed along internal staff traffic routes and should not have an isle with staff passing in front of the cabinet. These cabinets should not be placed near operational doors or general ventilation terminals.


2.       Cytopathology and Histopathology Laboratories:

2.1.     Storage capacity for cytopathology and histopathology slides, blocks and records is the major consideration. Storage capacity needs to be determined from the annual case-load.

2.2.     Consideration should be given to the adopting off-site storage. Off-site storage conditions and distances need to be assessed.

2.3.     Building structural capacity and floor loading should be considered for storage areas.

2.4.     Storage space for histopathology slides and blocks should be provided, based on annual workload.


3.       Microbiology Laboratories:

3.1.     Centrifuges generate significant noise and vibration. Large centrifuges can also consume considerable power and generate heat. These effects should be isolated so as not to affect the rest of the equipment or activities in the lab such as balances and microscopy.

3.2.     Balance tables should be provided for scales and balances.

3.3.     Microscopy work requires facilities for staining of slides and imaging. Dedicated benches which are free of rotating or vibrating equipment should be provided for imaging processes.

3.4.     Cell and Tissue Cultivation Laboratories:

3.4.1.  Dedicated cell culture laboratories may be required for genetics or virology testing.

3.4.2.  Cell culture and labs require 10-20 air changes per hour of EN779-F9 filtered air. Open samples should be manipulated in biosafety cabinets.

3.4.3.  In-vitro fertilisation (IVF) labs should be finished in non-VOC emitting materials and should be ventilated with activated carbon filtration. Ventilation equipment and components should additionally be non-VOC emitting.

3.4.4.  A cell culture laboratory for the cultivation of cells and tissues may be required if genetics and virology testing is planned. Class IIA1 biosafety cabinets in accordance with the WHO Laboratory biosafety manual, Third edition (2004) will be required for manipulation of samples.  The compulsory specification VC8041 published by government notice R93 (2001) requires a down-flow velocity of 0.5m/s for these cabinets. This velocity is, however, likely to affect scales operating within the cabinet. A selection of cabinets with a more moderate velocity in the range of 0.25 m/s is recommended as per the SANS 12469:2002.

3.4.5.   Cell and tissue cultivation laboratories should accommodate at least:

3.4.6.   one bench-mounted microscope

3.4.7.  an under-bench fridge and freezer

3.4.8.  a bench-mounted centrifuge

3.4.9.  a floor-standing incubator

3.4.10.                   a sink with associated services

3.4.11.                   separate hand wash basin with associated services

Point-of-care testing (POCT):

1.       Typical point of care testing equipment includes:

-         Reagent-impregnated strips

-         Single test equipment for glucose or cholesterol and

-         Fully automated instruments, such as blood glucose monitoring systems and blood gas/critical care analyser.

2.       Where point of care consulting areas are provided in a primary care areas these should be equipped with an examination couch, desk and chairs, wash-hand basins and point of care testing equipment.

3.       A point of care laboratory module should be 3m X 3m and allow for back-to-back working at laboratory benches as a minimum.

4.       A point of care laboratory module should include:

4.1.     a sink with associated services

4.2.     laboratory benching for testing equipment and computers

4.3.     floor space for under-bench refrigerators,

4.4.     separate wash-hand basin facilities

4.5.     storage space should for equipment and supplies

Storage

This section details location and spatial planning of storage areas for specimens, chemical reagents and other laboratory consumables, and assists in determining storage requirements per functional laboratory.

1.       Relevant storage space and conditions should be provided to ensure the continuing integrity of samples, slides, histology blocks, retained micro-organisms, documents files, manuals, equipment, reagents, laboratory supplies, records and results (SANS 15189:2009).

2.       Supplies and service equipment should be stored in non-laboratory support spaces

3.       Waste treatment and storage may be done at the laboratory or by non-laboratory support services.

4.       Separate storage facilities should be provided for the following:

4.1.     blood and blood products

4.2.     chemicals and reagents

4.3.     clinical material

4.4.     drugs, vaccines and other therapeutics

4.5.     hazardous substances

4.6.     process records

4.7.     quality records

5.       Storage and disposal of dangerous materials should be those specified by relevant standards and regulations (SANS 15189:2009).

6.       Sufficient space should be provided so that incompatible waste and non-waste chemicals and gases can be physically separated and stored.

7.       Compatible non-flammable laboratory chemicals could be stored together. These should be stored in a poisons cabinet where appropriate.

8.       A flammable material store can be provided for day-today storage of flammable chemicals.

9.       Bulk storage of flammable materials should be stored in a secure ventilated, flammable goods store that is external to, but easily accessible from the laboratories.

10.    Extremely and highly flammable liquids should be stored in accordance with Government Notice R1031 (1986)

11.    Refrigerators used for storage of flammable volatile solvents should have intrinsically safe or non-incendive motors, lighting and switchgear.

12.    Stores that are easily accessible from the relevant laboratory areas are required for working stocks of materials and equipment.

13.    The chemical store should have a preparation area for weighing and preparing reagents for use in the laboratory areas.

14.    Provision should be made for the storage of glassware and other equipment.

15.    Ergonomic and safety considerations should be made when designing laboratory shelving. A recommendation is given as follows (Stanford, 2011):

15.1. Shelving should not be installed which require laboratory staff to reach 30 cm above shoulder height, and extend arms greater than 30 cm while holding objects 16 kg or less when standing on the floor or on a 300mm stool

16.    Oxidising agents should not be stored on wooden shelves.

17.    A storage area for pressure vessels, compressed gas cylinders and pressurised manifolds where:

17.1. Gasses should be segregated by hazard class and flammable gases should not be stored with oxidizing agents.

17.2. They are protected from external heat sources, radiant heat, electric arcs or high temperatures.

17.3. They are in a well-protected, well ventilated, dry location, at least 6m from highly combustible materials

17.4. Refer to the Pressure Equipment Regulation of 2009 for further requirements.

Walls, doors and architectural details

This offers guidance on the planning, location and detailing of architectural details and furniture. This section should be read in conjunction with the IUSS Materials and finishes guidance document.

1.       The laboratory should be entirely enclosed within the walls floors and ceilings of a building. No functional clinical portion of the laboratory should include outside areas.

2.       Openable windows in clinical laboratories are discouraged. The WHO does however advocate naturally ventilated TB diagnostic laboratories and, should this concept be adopted, it should be a free-standing unit, physically isolated from the rest of the laboratory facility. Any openable windows should include security bars which do not impede the mechanical operation of the window and should also include insect and vermin screens.

3.       Laboratory doors should be fitted with automatic door closers and viewing panes. Emergency door should swing in the direction of egress and doors between rooms with a cascading pressure differential should swing in the direction of the higher pressure.

Open vs Closed Laboratories

This section addressed the requirement for modern modular laboratories to be designed around a concept of long term flexibility and the accommodation of unknown future laboratory trends and technologies.

1.       The long term strategy of any a laboratory within the healthcare service and the rapidly changing nature of laboratory technologies and practices should inform any planning of new or revamped facilities. While new technologies may bring the advantage of ever diminishing equipment sizes, the emergence of new equipment for previously manual or non-existent techniques has the counter effect of increasing the space and storage requirements for laboratories.

2.       With the trend towards automation of laboratory services new fully automated equipment can be large heavy and bulky. Present and future consideration should be given to providing contingency access for the installation and removal of such equipment. Provision of access and space should also be made for the inclusion of related support services.

3.       The provision of a generic open laboratory space can accommodate a range of pathology functions. This flexibility is maintained, even in an essentially unchanging or standardised repetitive framework of services, by relocating people and services within the space to accommodate new needs and equipment.

4.       A generalised lab arrangement should be developed during the design stage. This arrangement should be able to host the widest foreseeable range of services that may need to be presented at that laboratory.

4.1.     The design stage assessment of the physical aspects and requirements should include:

4.1.1.  Availability of space for alterations and additions, including office space and staff facilities.

4.1.2.  Type of construction and compliance with national building regulations.

4.1.3.  For retrofitting projects, the condition and age of the building and related engineering services.

4.1.4.  Fire precaution requirements

4.1.5.  Physical constraints such as load bearing walls and load capacity of floor slabs.

4.1.6.  Energy usage and available capacity.

4.1.7.  Decommissioning and disposal requirements. When selecting equipment, account should be taken of the use of energy and future disposal (care of the environment) (SABS, 2009).

4.2.    Modular furniture, adjustable height tables and movable furniture with standardised dimensions are beneficial as these enable the reconfiguring or removal of workstations as technology, processes and services change (InformeDesign, 2005).

Laboratory Equipment

This section addresses building infrastructure to accommodate laboratory equipment, including Laboratory Hoods and Fume Cupboards, Biosafety Cabinets, Fridges and Centrifuges.

1.                Laboratory Hoods, Fume Cupboards and Biosafety Cabinets

  1. Valves, electrical outlets and utility switches serving hoods should be placed at readily accessible locations and should be clearly marked.
  2. Planning of location and routes for the extraction ducting and services to the external extraction fan should be considered by the architectural team even if while the fume cabinet may be supplied by the laboratory service provider.
  3. Manifolding of fume hood exhaust ducting from adjacent laboratories should be avoided.
  4. Fume hoods should not be the sole means of laboratory room ventilation. The quantity of air extracted by fume hoods should be replenished with tempered outside air by a dedicated and interlocked mechanical ventilation system.
  5. Room air currents near the fume hood should not exceed 0.1m/s to ensure hood containment.
  6. Fume cupboards should not be positioned such that lab traffic and escape routes would not necessitate passing directly in front of the cupboard.
  7. The design, installation and operation of biosafety cabinets should comply with requirements of the following:

·        SANS 10226:2009 The installation, post-installation tests and maintenance of microbiological safety cabinets

·        SANS 12469:2002 Biotechnology - Performance criteria for microbiological safety cabinets

·        VC8041 2001 The compulsory Specification for Microbiological Safety Cabinets

2.                Refrigerators and freezers

  1. Refrigerators and freezers should not be located in one room unless the air-conditioning system can accommodate the high heat gain of this equipment.
  2. Where specimen and reagent storage capacity demands the use of cold rooms rather than refrigerators, these rooms should be maintained at +4˚C. These fridges should include insulated floor drainage and modular shelving.


Engineering Services

  1. Flexibility in the provision of support services such as electricity, water, vacuum and gasses can be achieved by the adoption of an open ceiling grid where neatly installed services can be easily identified, maintained and reconfigured as required. These services should be laid out on a regular grid with provision for regular connection points.

5.       Where services cannot be brought down through ceiling mounted pendants, floor mounted service islands or spines should be created to which mobile furniture and equipment can be attached.

1.                Waste Treatment and Disposal

1.       The management treatment and disposal of healthcare waste must be in accordance with the requirements of the SANS 10248 Management of healthcare waste, set of standards (SABS 2004). This set of standards includes:

1.1.     SANS 10248 Management of healthcare waste. This document specifies criteria for the segregation, collection, movement, storage and disposal of waste materials within health care.

1.2.     SANS 10248-1 Management of healthcare waste - Part 1: Management of healthcare risk waste from a healthcare facility. This document lays down minimum provisions for the safe and effective management of healthcare risk waste generated by healthcare facilities and other places where healthcare professionals work in order to reduce potential risks to humans and to the environment. The management of healthcare risk waste covers the generation, the packaging, the treatment and the disposal of waste.

1.3.     SANS 10248-2 Management of healthcare waste - Part 2: Management of healthcare risk waste for healthcare facilities and healthcare providers in rural and remote settings.

1.4.     SANS 10248-3 Management of healthcare waste Part 3: Management of healthcare risk waste from minor generators - Registered healthcare professionals and non-healthcare professionals

2.       Additional legislation and regulations that should be considered wen planning for the generation, treatment, disposal and transport of waste or materials that contain or potentially contains human pathogens

2.1.     All waste generated in the laboratory should be considered for safe disposal. Laboratory waste

2.2.     should be disposed of in observation of the following South African legislation:

2.3.     Hazardous Substances Act (Act 5 of 1973)

2.4.     Environment Conservation Act (Act 73 of 1989)

2.5.     Occupational Health and Safety Act (Act 85 of 1993)

2.6.     National Water Act (Act 36 of 1998)

2.7.     The National Environmental Management Act (Act 107 of 1998)

2.8.     Municipal Structures Act (Act 117 of 1998)

2.9.     Municipal Systems Act (Act 32 of 2000)

2.10. Mineral and Petroleum Resources Development Act (Act 28 of 2002)

2.11. Air Quality Act (Act 39 of 2004)

2.12. National Environmental Management: Waste Act, 2008 (Act 59 of 2008)

2.13. National Road Traffic Act, 1996 (Act 93 of 1996)

3.       The following considerations should be made when planning for laboratory waste discharge to the domestic sewer system:

3.1.     Even though most sewers are can accept a tolerable level of infectious material, the healthcare facility has a duty of care not to discharge healthcare waste other than domestic sewage to a domestic sewer. Where needs exist to discharge waste to the domestic sewer, provision shall be made to adequately treat the waste to make it safe for discharge.

3.2.     The following wastes shall not be discharged to the domestic sewer:

3.2.1.  listed chemicals such as mercury

3.2.2.  pharmaceutical waste

4.       Alternatives to direct disposal to domestic sewer, which can be planned for, include destruction and disinfection methods such as:

·        Incineration

·        Autoclaving

·        Microwaving

·        Chemical disinfection

5.       The size of the waste treatment and storage areas should be determined by the frequency of the collection and the amount of waste generated. This would be directly affected by the proximity of the facility to waste management service providers.

6.       Sharps should be discarded at point of use and sharps bins should be provided for this purpose.

7.       Biosafety level labs should have direct access to autoclaving facilities. These autoclaves should preferably be dedicated to the lab for waste management purposes.

8.       Chemistry labs shall implement chemical dilution traps within all sinks and hand wash basins. Transparent traps are preferable.

9.       Metal pipework is not suitable for use in pathology laboratories as these are subject to corrosion by discharged chemicals and biological waste. Non corruptible materials such as glass and plastics may perform better assuming the selection of a suitable solution gives consideration to the temperature of the discharged fluids, the corrosive and volatile nature of the discharge and the mechanical limitations of the material selected.

10.    Glass, polypropylene, and other plastics are suitable, but consideration should be given to the chemical characteristics, temperature of the fluids discharged, and arrangements for fixing and supporting the drain (Welsh Health Estates, 2005).

11.    The designer should liaise with the local authority to establish the maximum permissible discharge quantities of laboratory waste.

2.                General Utilities

This section discusses lab specific guidance relating to general engineering services and utilities. These utilities refer to electrical, plumbing and communications services. Design guidance of the building infrastructure for the location of general services. Design guidance could be specific to a functional laboratory and may infer from operational practices of the functional laboratory. For more specific guidance refer to the IUSS Building Engineering Services guidance document.

11.1. Lighting:

11.2. Laboratories should have adequate natural or artificial illumination to ensure visibility for diagnostic accuracy and operational safety. Uniformity of lighting and prevention of glare are as important at illumination levels.

1.       Electrical:

1.1.     Worktop, flush mounted electrical outlets are not recommended as these areas have a high potential for liquid spillage.

1.2.     Sufficient power outlets should be provided for the equipment planned including an additional contingency quantity.

2.       Plumbing:

2.1.     Drainage lines in the ceiling space of clean labs should be avoided. This pertains specifically to inspection and cleaning eyes.

2.2.     Hot and cold water systems:

2.2.1.  The floor below the emergency shower should be graded and drain into a suitable drainage point to prevent this water from running across the lab floor.

2.3.     The following guidance for drainage and waste systems is to be read in conjunction with Waste Treatment and Disposal above:

2.3.1.  Sink traps and piping to floor drops should be made of acid-resistant materials. Below ground, acid-resistant pipes should not be damaged by minor quantities of acids and solvents.

2.3.2.  Laboratory drain vents should be routed through the roof to outside and may not be manifold connected to sanitary vent piping

2.3.3.  Drainage lines from pathology laboratories should not be routed through other hospital accommodation such as critical care areas, operating theatres and catering departments as these drains can harbour high risk pathogens

2.3.4.  Autoclaves, with the exception of bio-secure autoclaves, should not be connected directly to the sewer drainage system but should be connected with an air gap using a tundish to prevent back-contamination.

2.3.5.  Waste lines from autoclaves should be designed with the temperature of the liquid discharge in mind. Where boiling water is discharged into sewer drainage or external gulleys, provision should be made for the management of any steam. High quantities of steam can travel back up the drainage system into adjacent areas.

2.3.6.  Floor gullies should be avoided.

3.                Ventilation

1.       The reader is advised to read this section in the context of the IUSS Building Engineering Services guidance document as many of the principles of airborne contamination control are introduced and developed therein.

2.       Where general laboratories require artificial ventilation they should have a minimum ventilation flow rate of 6 ACH. BSL2 labs and higher shall have a minimum ventilation rate of 12ACH (SANS 10400-O).

3.       The use of fan-coil or split air-conditioning units to reject internal heat gains is acceptable in general labs but not on cell culture or IVF labs. These labs would need a dedicated ventilations system providing fine filtered air and ventilation rates as described above.

4.       Laboratories must be maintained at a pressure negative relative pressure to the corridor and less hazardous adjacent areas.

5.       Air exhausted from laboratory work areas should be vented directly to outside and not into plant rooms, interstitial spaces, service shafts and ceiling voids.

6.       Where add air fume hoods are considered for their potential energy savings, these units should be specified and validated such that the add air system does not cause turbulence and flow reversal at the sash hood. Add air systems should be considered as potentially risky. Add air systems may also create a level of operator discomfort during seasonal extremes of climate.

7.       Side wall grilles and diffusers should not be used as these will disturb the cabinet performance.

8.       Doors should be fitted with door closers including a damped slow latching feature. Fast swinging doors can create a piston effect in rooms and disturb cabinet airflows and performance.

9.       No laboratory ventilation ductwork may be internally insulated by any means.

10.    Exhaust stacks from fume hoods or exhausting biosafety cabinets should extend and discharge vertically upwards at a height of 3m above the roof of the building without any risk or re-entrainment of that air directly into any ventilation system or openable window. Laboratory exhaust shall discharge at or below head height in any trafficable or technical areas. Discharge velocities of 15m/s are recommended.

11.    Where the building profile does not permit high level discharge, dilution systems with very high discharge velocities could be considered under careful design and a strict validation plan. The risks of such an approach should be well understood and managed.

11.1. Laboratory exhaust system fans should be located as near to the point of discharge as possible to ensure as much of the exhaust duct is under negative pressure as possible. All exhaust ductwork inside the building should be under negative pressure. Anti-backflow devices should be installed and discharges should be protected from high winds and adverse weather.

12.    Exhaust fans should be easily accessible for maintenance and should be clearly identified with durable weather proof labels indicating which laboratory and hood they are serving.

13.    A separation distance of 25m is recommended between laboratory exhausts and any ventilation opening.

14.    Staining areas should have bench extract systems that ensure air flows away from operator’s faces. Low-level extract should be provided adjacent to equipment for use when solvents are changed or when specimens in formaldehyde are opened (Welsh Health Estates, 2005).

4.                Security and Access Control

1.       Laboratory infrastructure design planning should include the location and planning of security control and access points. Design guidance could be specific to a functional laboratory and may infer from operational practices of the functional laboratory.

2.       Access to, and use of areas affecting the quality of examinations should be controlled. Appropriate measures should be taken to safeguard samples and resources from unauthorised access (SABS, 2009).

3.       Access should be restricted to authorised personnel only. This could be attained through security measures, such as swipe cards, or locks to controlled entry points.

4.       Use of biometric fingerprint scanning systems can fail in settings where the occupants are required to wear surgical gloves or regularly work with harsh chemicals. Alternative scanning systems should be considered.

Materials

1.       The reader is advised to read this section in the context of the IUSS Materials and Finishes guidance document as many of the principles of airborne contamination control are introduced and developed therein.

2.       Surface materials should be resilient to scratches and chemicals such as acids, alkalis, detergents, disinfectants, solvents and staining fluids.

3.       Cellulose based substrates for laminated surfaces are not permissible in cell culture and IVR labs. Cellulose based surfaces are not permissible in pathology laboratories.

4.       Bench tops are to incorporate a faint lip to prevent spillage from seeping onto the floor.

5.       Tiled walls and floors are not permissible.

6.       Fiberglass building surface finishes are not permissible.

7.       Laboratory facilities should be designed to facilitate as well as withstand easy, frequent and thorough cleaning. Surface finished should therefore be impervious, resilient and continuous.

8.       Continuous coved cornices are at wall and floor interfaces. Coving radiuses of 40mm are recommended. Larger radiuses could prevent furniture legs from fitting closely enough to the walls. The interface between permanent immovable furniture and the floor should similarly be coved.

9.       Walls should be coated with a hard non-porous paint finish.

Special Laboratories

This section only looks at biological laboratories. It excludes forensic, nuclear and radiological laboratories.

5.                Biological laboratories

1.       This design guidance document describes building infrastructure related to biological laboratories, up to and including Biosafety Level 2.

2.       This document should be read in conjunction with the infrastructural requirements for biological laboratories as set out in Regulation 178 of the National Health Act of 2003 (added 2 March 2012).

3.       For microbiology work, separate BSL3 laboratories are required if work is to be carried out on hazard group 3 organisms and specimens (R178).

Planning for Safety

1.       Door labelling should identify the type of lab and the responsible person including contact details

2.       A hand wash basin for hand washing must be included within each laboratory unless the environmental requirements of that laboratory prohibit it (ie aseptic areas). In special cases alternative hand sanitation measures can be provided although hand washing should not be precluded on leaving these laboratories. Hand wash basins should be fitted with stainless steel splash-backs fixed and sealed to the wall surface. Hand wash stations should also include a similarly fixed wall mounted mirror enabling the visual confirmation of the appropriate fitting of personal protective equipment.

3.       Laboratories hazards include:

·        Hazardous biological agents

·        Electrical fires due to the large amount of powered equipment

·        Quantities of infectious substances

·        Naked flames

·        Quantities of combustible materials, e.g. paper and packaging.

·        Slips and falls from spilled liquids on polished floor surfaces.

4.       In the event of an emergency, the laboratory may be unsafe to enter, therefore shut-off valves for gas and vacuum lines and electrical circuit breakers should be located outside the laboratory

5.       Plumbed or single use emergency eyewash stations should be provided in all laboratories.

6.       Emergency showers should be provided in all laboratories where a worker’s skin could become contaminated with infectious, skin irritant, toxic by skin absorption or corrosive materials.

7.       Eye wash stations and emergency shower locations should be identified with a highly visible signage.  The floor immediately beneath the eyewash station and emergency shower should have a distinctive colour or pattern to a radius of about 1m to enable staff to find them easily when their vision may be temporarily impaired. These areas should be well illuminated.

8.       Emergency showers should provide an immediate high-volume output of water. Emergency showers should be fitted with a timed, automatic shut off valve. Floor drainage needs to be provided at the emergency shower. Floor and wall mounted electrical services should not be located near emergency showers without sufficient protection.

Maintenance

1.       Wherever possible, maintenance items should be placed outside of the laboratory such that maintenance staff needn’t enter and disrupt the laboratory during the course of their work. This provision includes for items in the ceiling void and especially refers to services not related to that laboratory.

2.       A provisional maintenance budget and plan should be established and presented for review at the conclusion of the facility design stage. This plan should include equipment stock, staffing and skills requirements. This plan should be checked and updated on conclusion of validation and handover.

Validation and Accreditation

3.       SANAS accreditation SANS 14189 SAN17043 SANS 17025

4.       DTI Registration?

5.       Checklist



PART C – Room Data Sheets

Table 2:  TYPICAL ACCOMMODATION SCHEDULE (400 BED HOSPITAL)
Room Name Service Description Area

(m²)

Min. Ceiling Height

(m)

Occupancy

(Persons)

Nominal Utilisation per day

(hours)

Community space Reception and waiting areas 2.7 8
Male/Female/ Accessible Ablution areas Ablution areas – male  and female

One WHB per WC or urinal

3+ (per cubicle) 2.4 4
Lobby Circulation 2.7 4
Changing room Staff changing room - lockers to be provided 2.4 2
Tea Room 2.7 2
Storage space Equipment and samples storage space


2.8 1 8
Administration Daily administration functions 2.8 8
Pre-analytical /

Specimen Reception

receive samples, capture and process test request and distribute the samples 2.8 8
Clinical –

Cyto Genetics

Pathology 2.8 8
Clinical –

Molecular Biology

Pathology 2.8 8
Clinical – Microbiology Pathology 2.8 8
Clinical – Chemistry Pathology 2.8 8
Clinical – Haematology Pathology 2.8 8
Waste Management Storage and treatment of waste 2.8 [TVR@2] 4


Table 3: LABORATORY ROOM SERVICES
Room Name Temp

(°C)

Ventilation

(AC/h)

Ventilation

Type

Pressure Relative to

Ambient

Wet Services SSO

400V

SSO

230V

Task Illuminance

(lux)

Data Points Colour Rendering

(Ra)

Community spaces 21-25 12 Forced

Extraction

= 300 -
Ablution areas 21-25 10 Forced

Extraction

- WC

WHB

300 -
Lobby N/A 2 Forced

Supply

= 300 >80
Changing room 21-25 2 Forced

Supply

= WHB 300 -
Tea Room 21-25 10 Forced

Supply

= CW

HW

300 -
Storage space 22-25 4-40 Forced

Supply

- - 300 -
Administration 21-25 2 Forced

Supply

= - 300/500 >80
Pre-analytical/

Specimen Reception

21-25 12 Supply/

Extraction

= WHB

EW

500 >90
Clinical – Cyto Genetics 21-25 6 Supply/

Extraction

- WHB

EW

500 >90
Clinical – Molecular Biology 21-25 6 Supply/

Extraction

- WHB

EW

500 >90
Clinical – Microbiology 21-25 6-20 Supply/

Extraction

+ WHB

EW

500 >90
Clinical – Chemistry 21-25 6 Supply/

Extraction

- WHB

ES, EW

500 >90
Clinical – Haematology 21-25 6 Supply/

Extraction

- WHB

EW

500 >90
Waste Management 21-25 12 Forced

Supply

- WHB

EW

500 [TVR@3] -



Table 4 LABORATORY ROOM FINISHES
Room Name Floor

Material

Wall / Floor Interface Walls

Finish

Ceiling

Finish

Doors

Type

Community spaces - - - Acoustic ceiling board Lockable solid door
Ablution areas Tile Skirting finished as per floor Ceramic wall tiles with epoxy grout Acoustic ceiling board No requirement
Lobby Tile Skirting coved and finished as per floor Washable acrylic paint Acoustic ceiling board No requirement
Changing room Vinyl Skirting coved and finished as per floor Washable acrylic paint Acoustic ceiling board No requirement
Tea Room Tile Skirting coved and finished as per floor Washable acrylic paint Acoustic ceiling board No requirement
Storage space Jointless vinyl sheet Skirting coved and finished as per floor Washable acrylic paint Washable acrylic paint Lockable door
Administration Tile Skirting finished as per floor Washable acrylic paint Acoustic ceiling board Lockable door
Pre-analytical/

Specimen Reception

Jointless vinyl sheet Skirting coved and finished as per floor Washable acrylic paint Vinyl clad ceiling tiles Lockable door with door closer
Clinical – Cyto Genetics Jointless vinyl sheet Skirting coved and finished as per floor Washable acrylic paint Impervious monolithic, Washable acrylic paint Lockable door with door closer
Clinical – Molecular Biology Jointless vinyl sheet Skirting coved and finished as per floor Washable acrylic paint Impervious monolithic, Washable Lockable door with door closer
Clinical – Microbiology Jointless vinyl sheet Skirting coved and finished as per floor Washable acrylic paint Impervious monolithic, Washable Lockable door with door closer
Clinical – Chemistry Jointless vinyl sheet Skirting coved and finished as per floor Washable acrylic paint Impervious monolithic, Washable Lockable door with door closer
Clinical – Haematology Jointless vinyl sheet Skirting coved and finished as per floor Washable acrylic paint Impervious monolithic, Washable Lockable door with door closer
Waste Management Self- levelling epoxy Skirting coved and finished as per floor Washable acrylic paint Impervious monolithic, Washable Lockable door with door closer



PART D – EXAMPLES        

The following examples are provided courtesy of the National Health Laboratory Services.

Figure 3 Example of Central Lab - Vryheid


Figure 4 Example of Modular Lab

List of Abbreviations

ACH Air changes per hour
BSC Biosafety cabinet
BSL1 Biosafety level 1
BSL2 Biosafety level 2
BSL3 Biosafety level 3
BSL4 Biosafety level 4
OH&S Occupational Health and Safety
WHB Wash Habd Basin
ES Emergency Shower
EW Eye Wash
WC Toilet (Water Closet)
POCT Point-of-care testing

List of Definitions

Acceptable Risk Risks that have been reduced to a level that can be tolerated by the organisation having regard to its legal obligation and its own OH&S policy (SABS, 2011)
Anatomical Pathology Involves the analysis of dead body tissues and cells (InformeDesign, 2005).
Biosafety code A means of classifying human pathogens into categories according to the risk posed by that pathogen or a manipulation of that pathogen (National Department of Health, 2012).
Biosafety level 1 A laboratory working with defined and characterised strains of viable infectious agents not known to cause disease or colonise in healthy human adults. However, these strains may be opportunistic and cause infection in the young, aged, and in immunocompromised or immunosuppressed individuals (National Department of Health, 2012).
Biosafety level 2 A laboratory working with a broad spectrum of indigenous moderate-risk agents present in the community and associated with human disease of varying severity. Activities with low aerosol potential with these agents can be conducted on an open bench using good microbiological techniques. Procedures with high aerosol potential may increase the risk of exposure of personnel to infectious aerosols and must be conducted in primary containment equipment or devices (National Department of Health, 2012).
Biosafety level 3 A laboratory working with indigenous or exotic agents which may readily cause serious and potentially lethal infections. Primary hazards to personnel working with these agents relate to auto-inoculation, ingestion and exposure to infectious aerosols (National Department of Health, 2012).
Clinical Laboratory A laboratory for the biological, microbiological, immunohaematological, haematological, biophysical, cytological, pathological or other examination of materials derived from the human body for the purpose of providing information for the diagnosis, prevention and treatment of disease in, or assessment of the health of, human beings, and which may provide a consultant advisory service covering all aspects of laboratory investigation including the interpretation of results and advice on further appropriate investigation (SABS, 2009).
Clinical Pathology Involves the analysis of bodily fluids, usually urine or blood (InformeDesign, 2005). Common clinical pathology diagnoses include blood cell counts, coagulation studies and blood glucose level determinants (InformeDesign, 2005).
Corrective Action An action to eliminate the cause of a detected nonconformity or other undesirable situation (SABS, 2011).
Diagnostic specimen Any human or animal material, which extends to excreta, secreta, blood and blood components, tissue or tissue fluids, that may be used for the purpose of diagnosis. This definition does not extend to live infected animals (National Department of Health, 2012).
Hazard A source, situation or act with a potential for harm in terms of human injury or ill health, or a combination of these (SABS, 2011).
High containment laboratory A laboratory which has special engineering features providing a safe environment for personnel to handle hazardous materials without posing danger to themselves, the community and environment  (National Department of Health, 2012). These engineering features may extend to access control and special ventilation systems (National Department of Health, 2012).
Incident Work related events in which an injury or ill health, regardless of severity, or fatality occurred, or could have occurred (SABS, 2011).
Laboratory Management Person(s) who manage the activities of a laboratory headed by a laboratory director (SABS, 2009)
Medical Laboratory See Clinical Laboratory
Microbiological laboratory A laboratory which handles human pathogens capable of colonising in humans. It includes laboratories which handle infected or infested, or potentially infected or infested, indigenous vectors of human pathogens, or exotic vectors, irrespective if they are infected or infested (National Department of Health, 2012).
Nonconformity Non-fulfilment of a requirement (SABS, 2011).
Occupational Health and Safety Conditions and factors that affect, or could affect, the health and safety of employees or other workers (including temporary and contract workers), visitors, or any other person in the workplace (SABS, 2011).
Risk Combination of the likelihood of an occurrence of a hazardous event or exposure and the severity of injury or ill health that can be caused by the event or exposure (SABS, 2011).
Workplace Any physical location in which work related activities are performed under the control of the organisation (SABS, 2011).



Acknowledgements

Special acknowledgement goes to the team responsible for researching and compiling this guidance document:

Etienne le Roux, NHLS;

Zibusiso Masuku, NHLS;

Faatiema Saalie, CSIR;

Tobias van Reenen, CSIR;

Hennie le Roux, NDoH,

Awaatief Railoun, NDoH


Bibliography

InformeDesign. (2005). Implications: Change in Clinical Labs in Hospitals.

National Department of Health. (2012). National Health Act 2003 - Regulations relating to the registration of microbiological laboratories and the acquisition, importation, handling, maintenance and supply of human pathogens.

SABS. (2009). SANS 15189:2009 Edition 2 Medical Laboratories - Particular requirements for quality and competence.

SABS. (2011). SANS 18001:2011 Occupational health and safety management systems - Requirements.

Stanford. (2011). Stanford Laboratory Standard & Design Guide : General Requirements for Stanford Laboratories. Version 2.0.

Wales Department of Health. (2006). HTM 05-03: Operational Provisions Part G: Laboratories on healthcare premises.

Welsh Health Estates. (2005). Health Building Note 15 – Facilities for Pathology Services. 2nd Edition.


[TVR@1]Please complete?

[TVR@2]Please complete sizes and occupancy

[TVR@3]Complete SSO & data

  1. InformeDesign. (2005). Implications: Change in Clinical Labs in Hospitals