Guidelines for safe sputum collection
Please help to expand this page. The reason given is: Article still under active review |
Contents
- 1 Introduction
- 2 Engineering control measures for sputum collection
- 2.1 Local exhaust ventilation devices
- 2.2 Sputum collection room
- 2.3 Testing of LEV devices and sputum collection room
- 2.4 Test Methods
- 2.5 Location of LEV devices and sputum collection room
- 2.6 Operation procedure and waiting time between usage: LEV devices and sputum collection room
- 2.7 Outdoor naturally ventilated sputum collection site
- 2.8 Location of outdoor site
- 2.9 Decision chart for procurement
- 2.10 References
Introduction
Sputum specimen examination is the main diagnostic procedure for pulmonary Tuberculosis [1]; however, the medical procedure (patient coughing) that is used for sputum collection increases the potential for transmission of M. Tuberculosis significantly [2]; therefore, there is need to administer sputum collection safely in healthcare facilities [3]. The CSIR’s Infrastructure Innovation research group has conducted many TB risk assessments in South African public healthcare facilities for over 10 years. A common finding was that engineering controls for sputum collection were not always adequate, maintained or monitored. Sputum was observed to be collected from toilets, consulting rooms and counselling rooms which implies increased risk of TB transmission. This guideline provide guidance on conducting sputum collection safely for suspected or known infectious TB patients. Although there is a three level hierarchy of control measures; administrative controls, engineering controls and personal respiratory protection to prevent transmission of TB, this guideline is limited to engineering control measures for sputum collection.
Engineering control measures for sputum collection
There are two main types of engineering methodologies that can be utilized for sputum collection; local exhaust ventilation devices and sputum collection/induction rooms.
Local exhaust ventilation devices
Local exhaust ventilation devices capture of airborne contaminants at or near the source before they are dispersed into the work space [4][5]. The basic components of an LEV device are hood, ductwork, air cleaner and fan [5]. Burgess, et al.,[4] identifies two major categories of LEV devices; enclosures and exterior. The major difference between these two is that for enclosures, contaminants are released from inside the device whereas for exterior contaminants are released outside the device. A sputum booth is considered as an example of an enclosure LEV device. Illustrations of an enclosure and exterior LEV devices are shown in Figures 1 and 2 respectively. Figure 1 shows a CSIR designed sputum booth. Technical specifications for the booth that can be used for procurement are included in Appendix A.
Table 1 gives a comparison between enclosure and exterior LEV devices.
Table 1. Comparison between enclosure and exterior LEV devices
Local Exhaust Ventilation device | Advantages | Disadvantages |
Enclosure
Contaminants are released from inside the LEV device. Example is a booth as illustrated in Figure 1. |
|
|
Exterior
Contaminants are released from outside the LEV device. Example is illustrated in Figure 2.
|
|
|
Sputum collection room
Testing of LEV devices and sputum collection room
Testing and monitoring of the LEV devices and sputum collection rooms is done to ensure correct continued operation of the systems.
Test | Engineering control | Recommended frequency of testing | Test method | Apparatus | Perfomance specification guideline/ standard |
---|---|---|---|---|---|
Air pressure difference | Sputum induction room, Enclosure LEV | Daily inspection | 2.4.1 | Electronic micromanometer, mechanical differential pressure gauge (magnehelic gauge) | Greater than -2.5Pa[6]. |
Total air flow rate measurement | Sputum induction room, Enclosure LEV | Once every 6 months | 2.4.2 | Flowhood with flowmeter or a combination of flowhood and anemometer (thermal or vane) | Greater than or equal to 12 ACH for sputum induction room[6]. |
Airflow direction and visualisation | Sputum induction room, Enclosure LEV | Daily inspection | 2.4.3 | Silk thread, Smoke Tubes, nicotine free electronic cigarettes. | Air should flow into the room and into LEV[6] |
Installed HEPA filter system leakage | Enclosure LEV | Once every 6 months | 2.4.4 | Aerosol generator as per ISO 14644:3 section C.6.3 and aerosol photometer | Filter penetration should not exceed 0,05% as per EN1822 standard. |
Test Methods
Air pressure difference test
The test is perfomed to verify the capability of the enclosure LEV and sputum induction room to maintain the specified pressure difference with respect to adjacent spaces. The test should be done with all doors closed. Permanent measuring points should be installed.
Total air flow rate measurement
Measurement of total airflow rate is carried out to calculate the clean air volume supplied to the Sputum induction room and Enclosure LEV per unit time, and this value can be used to calculate the air changes per unit time and airborne particle clearance times.
Airflow direction and visualisation
The purpose of airflow direction tests and visualisation is to confirm that the airflow direction conform to the design and performance specification and also to test for stagnant zones of sputum induction room and Enclosure LEV.
Installed HEPA filter system leakage
The test is perfomed to confirm that the HEPA filter is properly installed by verifying the absence of bypass leakage in the installation and that the filter is free of defects (small holes and damages in the filter medium and frame seal). The test is perfomed by introducing a 0.5µm to 0.7µm (as per ISO 14644:3 section B.6.2.2) aerosol upstream and scanning downstream of the filter.
Maintenance of LEV devices and sputum collection room
Location of LEV devices and sputum collection room
Operation procedure and waiting time between usage: LEV devices and sputum collection room
Outdoor naturally ventilated sputum collection site
Location of outdoor site
Privacy
Decision chart for procurement
References
- ↑ Hansen, D. J., 1993. The Work Environment: Healthcare, Laboratories and Biosafety, Volume 2. Lewis publishers: USA.
- ↑ Centers for Disease Control and Prevention. Guidelines for Preventing the Transmission of Mycobacterium tuberculosis in Health-Care Settings, 2005. MMWR 2005;54(No. RR-17).
- ↑ Infrastructure Unit Support Systems (IUSS), 2014. IUSS HEALTH FACILITY GUIDES: TB Services. South Africa. National Department of Health.
- ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 Burgess, W.A., Ellenbecker, M.J., and Treitman, R.D. 2004. Ventilation for control of the work environment. Second edition. New Jersey USA. John Wiley & Sons
- ↑ 5.0 5.1 Heinsohn, P. 1996. Tuberculosis resources guide CEC Report CR 106146. Carlifonia. USA. Heinsohn Consulting services.
- ↑ 6.0 6.1 6.2 Sehulster LM, Chinn RYW, Arduino MJ, Carpenter J, Donlan R, Ashford D, Besser R, Fields B, McNeil MM, Whitney C, Wong S, Juranek D, Cleveland J. Guidelines for environmental infection control in health-care facilities. Recommendations from CDC and the Healthcare Infection Control Practices Advisory Committee (HICPAC). Chicago IL; American Society for Healthcare Engineering/American Hospital Association; 2004.