Adult Inpatient Services
Contents
- 1 POLICY AND SERVICE CONTEXT
- 2 PLANNING AND DESIGN
- 2.1 1. Design and planning principles
- 2.2 2. Design and planning principles
- 2.2.1 2.1. General design and planning principles
- 2.2.2 2.2. Human resources
- 2.2.3 2.3. Nursing models of care
- 2.2.4 2.4. Unit management and administration
- 2.2.5 2.5. Teaching and training
- 2.2.6 2.6. Access and circulation
- 2.2.7 2.7. Infection control
- 2.2.8 2.8. Airborne infection isolation and protective environments
- 2.2.9 2.9. Ergonomics in design
- 2.2.10 2.10. Universal access
- 2.2.11 2.11. Telecommunication and IT systems support
- 2.2.12 2.12. Wayfinding and signage
- 2.2.13 2.13. In the inpatient facility
- 2.2.14 2.17. Ventilation and air management
- 2.2.15 2.18. Day- and night-time illumination
- 2.2.16 2.19. Fire detection and alarms
- 2.2.17 2.20. Security
- 2.2.18 2.21. Supply and disposal
- 2.2.19 2.22. Medication management
- 2.2.20 2.23. Options for dispencsing within the inpatient unit
- 2.2.21 2.24. Equipment cleaning
- 2.2.22 2.25. Storage - equipment
- 2.2.23 2.26. Storage – sterile supplies and consumables (sterile and surgical stores)
- 2.2.24 2.27. Storage of patients' belongings
- 2.2.25 2.28. Waste management
- 2.2.26 3. Inpatient unit acivities
- 2.3 4. Client expectations
- 2.4 5. Location and inter-departmental relationships
- 2.5 6. Flow patterns
- 2.6 7. Functional zones
- 2.7 Functional relationships within the inpatient unit
- 2.8 9. List of rooms
- 2.9 10. Room requirements
- 2.9.1 10.1. Bed unit – standard patient area
- 2.9.2 10.2. Location and relationship
- 2.9.3 Staff capacity
- 2.9.4 10.4. Patient activity
- 2.9.5 10.5. General requirements
- 2.9.6 10.6. Space requirements
- 2.9.7 10.7. Bed services
- 2.9.8 10.8. En suite sanitary facilities
- 2.9.9 10.9. Assisted shower
- 2.9.10 10.12. Treatment room
- 2.9.11 11.2. Clean utility
- 2.9.12 11.5. Dirty utility
- 2.9.13 11.8. Nurses’ station
- 2.9.14 11.9. Patient kitroom
- 2.9.15 11.12. Store for consumables
- 2.9.16 11.13. Equipment store
- 2.9.17 12.3. Staff toilet
- 3 PART C - ENGINEERING CONSIDERATIONS
- 4 PART D - STANDARD COMPONENTS
- 5 LIST OF ROOMS
- 6 LIST OF ABBREVIATIONS
- 7 REFERENCES
POLICY AND SERVICE CONTEXT
1. Policy context
Adult inpatient units provide suitable accomodation for the patient where diagnosis, medical and nursing care, and treatment can be provided effectively and economically.
The adult inpatient unit is the clinical unit in a hospital where patient bed space and clinical treatment space is combined. This combination allows the unit to provide patients with an effective, economical therapeutic unit for clinical diagnosis, medical treatment, and nursing care.
The inpatient unit environment needs to meet the requirements for safe nursing and clinical practice, adhere to health and safety standards, and meet recognised infection control principles, while maintaining the principle of patient privacy and dignity.
This document provides guidance on inpatient unit spaces and it should be read in conjunction with the full IUSS set of standards pertaining to an inpatient unit. Variations to the set standard for inpatient units will be noted where indicated.
Specialised guidelines for inpatient units for paediatrics, infectious diseases, i.e. tuberculosis, intensive care, obstetrics, rehabilitation, burns care, oncology and mental health care will be addressed in separate IUSS documents.2. Service context
The business case and the health brief define the correct package of services and the required bed distribution per facility based on the Provincial Strategic Transformation Plan and the government policy document:Government Notice R. 185, 2 March 2012, National Health Act 61/2003Regulations: Categories of hospitals: No.35101
District hospital | Regional hospital | Tertiary hospital | Central hospital | Specialist hospitals |
---|---|---|---|---|
General medical | Medical-Internal Medicine | Subspecialty Medical | Super specialties in the disciplines listed for tertiary care, including oncology | Tuberculosis(TB) Mental Health
Rehabilitation Infectious Diseases |
General surgical | General surgical | Subspecialty Surgical | ||
Specialty Surgical:
Gynaecology Orthopaedics Ophthalmology |
Subspecialty Surgical:
Gynaecology Orthopaedics Ophthalmology
| |||
Paediatric | Paediatric | Subspecialty Paediatric | ||
Maternity | Maternity | Subspecialty Obstetrics | ||
High careӿ | High careӿ | |||
Intensive Care Unitӿ | Intensive care underӿ supervision of a specialist intensivist | Specialist intensive careӿ | ||
Mental Health
Observation Room and 72 hours beds |
Psychiatric
Inpatient Unit |
Specialist psychiatric |
*To be dealt with in separate documents
2.1. Determining inpatient unit size
All inpatient units should function as stand-alone units. These units contain one, two or four bed-, with six-bed configurations only being permissible in certain instances.
The inpatient unit should be planned to operate at an optimal occupancy level considering the model of care to be provided, staffing strategies, staff availability and operational aspects.
2.2. Hours of operation
2.3. Patient visitors
2.4. Personnel
Facility management, such as food services, linen services, cleaning services and maintenance support, is performed on a daily, weekly or intermittent basis.
Visiting, teaching and volunteering activities may also take place within the inpatient unit space.
2.5. Operational policies
The following policies are relevant to inpatient units:
• Admissions | • Infection control |
• Amenities for patients and visitors | • Linen management |
• Amenities for staff | • Maintenance and engineering |
• Cleaning | • Medication management |
• Clinical information | • Operating hours |
• Communication systems | • Pastoral care |
• Complaints | • Risk management |
• Recording of patients data | • Safety and security |
• Disaster planning | • Sterilising services |
• Discharge of patients | • Stores and supplies |
• Equipment storage | • Waste management |
• Food services | • Others to be determined |
PLANNING AND DESIGN
1. Design and planning principles
Part B contains planning and design guidance, design considerations, functional relationships between hospital departments with respect to adult inpatient accommodation (inpatient units), and relationships within the inpatient unit itself.
Workflow diagrams are provided to explain the flow of patients, clinical staff, support goods and services, maintenance staff, as well as the public. Workflow diagrams within departments are provided to assist in understanding the intradepartmental relationships that support the functional flow in the inpatient unit to ensure productive service delivery.
The detailed room diagrams with accompanied norms and standards are provided to clarify understanding of the different space requirements and room specific specifications for an adult inpatient unit.
2. Design and planning principles
2.1. General design and planning principles
- Inpatient accommodation forms the core of a hospital and has functional relationships with most departments
- Patients enter the facility as inpatients, day patients or outpatients.
- The planning of the inpatient units should support planning principles that promote a holistic healing environment with, where possible, clear external views, consideration of noise levels, natural ventilation, as much morning sun or light as possible, and spaces that would create a pleasant healing environment.
- The design should reduce noise in the facility
- The design should make maximum use of natural light and views for patients and staff.
- The healthcare patient environment should be clinically safe and effective.
- The design should maximise patient safety and reduce the risk of errors and accidents.
- The work environment should be ergonomically safe and risk free.
- The design should avoid large sprawling layouts that are both resource and cost intensive.
- Workflow should be efficient and support effective resource utilisation.
- Appropriate space norms and room design should be implemented.
- The unit should comply with quality assurance principles.
- The unit should have communication and information systems that will support patient management and administration.
- Layouts should reflect the service needs of the patients in the inpatient unit.
- Beds should be clustered to facilitate staff efficiency, meal relief and optimal patient supervision, particularly at night when staffing levels are lower.
- The design should facilitate the delivery of care at the patient’s bedside or be proximal to the bedside whenever possible. This includes suitable services and supplies at the bedside.
- The environment should be aesthetically pleasing for patients and should assist staff in performing the required activities in the most efficient and supportive environment.
- Staff should not have to walk far to obtain supplies and equipment.
- The design should balance requirements for clinical need, and capital and recurrent budget considerations.
- The orientation of the inpatient units and aspect of inpatient accommodation should be prioritised in the development of the master plan. The orientation of the inpatient units should preferably face north or northeast, but a southern orientation is acceptable.
- If the prevailing wind direction is south, east and west orientations of inpatient units are discouraged.
- The placement of inpatient units must ensure patient privacy. Visitors, staff and service traffic through the inpatient units should be avoided.
- Inpatient units can be organised on the same level over a large floor area or they may be stacked into a multistorey block separate from diagnostic and treatment facilities, but closely linked. This allows more consistent planning of inpatient accommodation, increases flexibility in the way that beds can be organised, and enables maintenance and refurbishment to be carried out more easily.
- All pipes for sanitary requirements should be placed on external walls. Service support facilities and top-up of stores or pharmaceuticals and food delivery should be accessible to the inpatient units without compromising privacy or noise levels.
- The design should enable greater levels of observation in response to increased patient acuity.
- There should be enough space for activity at the bedside and other activities in the inpatient unit.
- There should be adequate storage space for bulky equipment.
- The area should be accessible to physically and sensory impaired people.
- The design should that make it possible to communicate administrative or clinical information from the bedside.
- The design should consider staff members’ and patients’ privacy for clinical treatment, bodily functions, personal care, and personal discussions and telephone calls
- Personnel – How many people are there at any given time in a specific place to perform a specific task or procedure?
- Activities – What procedures should be performed?
- Equipment – What equipment is required that will occupy the space?
- Security – What access control measures does the hospital management determine?
2.2. Human resources
2.3. Nursing models of care
Nursing care is the main activity that allows the effective and efficient functioning of the inpatient unit. The inpatient unit design should therefore ensure maximum patient observation and contact, with short travel distances for the staff.
Inpatient units should have no less than two single-bed units or more than four single-bed units per 32-bed inpatient unit.
2.4. Unit management and administration
If there is a ward clerk, he or she needs to be placed at the entrance to the ward and preferably at a small reception counter or at the nurses’ station. If the ward clerk is placed at the nurses’ station, additional space must be provided to accommodate the activities of the ward clerk.
The province’s policy with regard to staff facilities should indicate whether an inpatient unit staffroom or a shared restroom between inpatient units would be preferred. Staff toilets should be provided in each inpatient unit.
2.5. Teaching and training
2.6. Access and circulation
Service staff may access the ward through a second entrance, but it should be monitored for both safety and security. Waste should exit separately.
2.7. Infection control
Infection control considerations must include all healthcare workers. All areas of the facility shall be designed, constructed, furnished and equipped in keeping with the principles of infection control
The following aspects contribute to effective infection prevention and control and are relevant within the context of an inpatient unit:
- Hand hygiene facilities should be provided in all patient care areas, clinical areas and nurses’ stations.
- Hand hygiene facilities should be provided in areas where careful attention to hygiene is essential, such as kitchens, sluice rooms, utilities, medicine areas, bathrooms, toilets and change rooms.
- Hand basins must be visible to staff on entering and leaving the room. In addition, antibacterial hand rub dispensers should be provided at the entrance to each inpatient unit. Hand-wash facilities should also be placed in the main passage of the inpatient unit and next to the nurses’ station.
- Facilities should be provided to isolate infectious patients.
- The following facilities should also be provided:
- Linen handling
- Separation of clean and dirty work flows
- Storage
- Waste management
- Ventilation
- Surface finishes
- Careful aseptic technique and the observance of ‘standard precautions’
- The administrative infection control measures and protocols of the hospital should be followed and implemented in the design
2.8. Airborne infection isolation and protective environments
Protecting staff and visitors from infectious diseases is an important aspect of airborne infection isolation (AII). It should not be assumed that a well-designed and functional ventilation system provides sufficient protection for these persons. Personal protective equipment such as N95 or FFP2 respirators should be provided to all staff and visitors entering AII rooms. Where these persons are expected to enter such environments regularly, these persons should have themselves fit tested for respirator use.
Ceilings in AII and protective environment (PE) rooms shall be impervious monolithic structures to ensure excellent sealing and airtightness. Ceiling voids above these rooms, especially PE rooms, can be particularly hazardous spaces.
All swing doors shall be equipped with door closers to ensure that they remain shut when not in use. Hold-open devices are not recommended for these doors. Sliding doors are also not recommended as these pose difficulties in maintaining an adequate seal.
It is recommended that isolation rooms be provided with outside views where possible, without presenting a biosecurity risk. Privacy blinds should be installed, but these should not present a hygiene risk or hinder the nursing staff view of the patient.FIGURE 1: NEGATIVE PRESSURE ISOLATION
Convergent fluctuations of only 5 Pa in each of two adjacent rooms can potentially reduce the pressure differential between the rooms by 10 Pa. For this reason, pressure differentials of 15 Pa between rooms are recommended. Lower pressure differentials are easier to achieve, but offer less safety under normal operational fluctuations condition.
The use of visual air pressure monitors between the passage and the isolation room is required. This enables a constant visual indication of the airflow direction between the isolation room and adjacent areas. These monitors should indicate the pressure magnitude, direction and out-of-specification failure limits. All major ventilation system components serving these areas should be clearly marked with the room identification, system identification and a biohazard sign.
Supply and extraction systems should be interlocked so that a failure of the exhaust air system shuts the air supply off, preventing the isolation room from going into an overpressure status. It is acceptable to install a balanced-blade pressure stabiliser to ensure that the room does not experience extremes of pressure under supply fan failure, control system failure, or severe transient environmental conditions. However, the inclusion of these devices can increase the design capacity of the system under normal operation.
Additional information regarding engineering services design and planning for airborne precaution rooms can be found in the IUSS Building Engineering Services Guideline.[1]
FiGURE 2: PROTECTIVE ENVIRONMENT- POSITIVE PRESSURE
A PE room is required for patients who are immunocompromised, but do not initially present with an airborne infectious disease. These rooms require an anteroom to ensure a clean environment in the PE room. Where these are located within open wards,such as high-care units (HCUs) or intensive-care units(ICU), and are held at pressure positive to adjacent rooms, they should include negative pressure anteroom to prevent the potential spread of infection out of the PE room. This is a typical scenario for a burns ward. Where airborne infection risk is suspected in these rooms, staff and visitors entering the PE room should wear respirators prior to entering the anteroom.Additional ventilation measures, such as air that was filtered using high-efficiency particulate abosorption (HEPA), filtered supply air may be required when treating allogeneic patients.
FiGURE 3: AIRBORNE INFECTION PROTECTIVE ISOLATION
Where patients are immunocompromised and initially suspected of presenting with an infectious airborne disease, they should be located in an airborne infection protective isolation room. These rooms shall be designed to maintain a negative pressure relative to the anteroom and adjacent rooms, with the exception of the en suite bathroom. These rooms demand very low air permeability with high-quality sealing. The Centres for Disease Control (CDC) Guidelines for Environmental Infection Control in Health Care Facilities (2003) recommend an effective leakage area of less than 0.045 m² for the entire room. Placing this in context, the equivalent gap for a single half-leaf door that has been hung relatively well is calculated in the order of 0.04 m².
Respiratory protection needs not be worn in the anteroom in this scenario, as the anteroom is held at a relative pressure positive to the patient room.
While it may be tempting to develop positive pressure protective isolation rooms that can be adjusted to operate as negative pressure protective isolation rooms for airborne infection control, this practice is strongly discouraged, since it presents the inevitable scenario where the room is operated in an inappropriate mode for the wrong case, which places many people at risk of infection. The operation of neutral pressure rooms as a compromise is also not recommended as the negligible room permeability required for these rooms is not easily achieved or maintained.
2.9. Ergonomics in design
Designers should consider the optimum comfort of all situations for staff, patients and visitors.
Refer to:
- Alder, D. and Tutt, P. eds., 1992. New metric handbook : Planning and design data. Oxford: Reed Educational and Professional Publishing Ltd.
- Neufert, E. and Neufert, P., 2012. Neufert architects’ data. 4th ed. New York: John Wiley & Sons.
2.10. Universal access
- Mobility impaired
- Visually impaired
- Hearing impaired
2.11. Telecommunication and IT systems support
- Telecommunication system
- Nurse call to all patient areas with central control system
- Paging and personal telephones replacing some aspects of call systems
- Bar coding for supplies, X-rays and records
- Computer network connections in all management and patient administration and information systems:
- Hospital information system (HIS) and electronic patient records
- Patient administration system (PAS)
- Radiology information system (RIS) (digital X-rays)
- Picture archiving communication system (PACS)
- Laboratory with a link to the National Health Laboratory Service (NHLS)
- Pharmacy system
2.12. Wayfinding and signage
It is important to plot the various routes patients, visitors, suppliers and staff may have to travel to get to the inpatient facility from the car park, drop-off points and other departments in the hospital. Once these routes are established, principles can be applied to the design to assist successful wayfinding.
Ways to enhance wayfinding include the following:
- Printed information (pamphlets
- Architectural features and design elements that provide clues as to what the function of the building is and can include landscaping, sculptural features and architectural interior design
- Floor covering, lighting, wall, door and window graphics
- Permanent signage
- Digital devices (e.g. kiosks or information screens)
- Human interaction (e.g. human interaction at help desks)
The following core principles should be adhered to:
- Design that includes everyone, especially those who are more vulnerable, such as the following:
- The first-time visitor
- The physically challenged
- Those with some form of impairment
- Children
- Utilisation of standardised information systems
- Utilising ‘key hub’ destinations along a complex journey (a person is directed to a primary hub destination then directed on to a secondary hub destination from that point)
- Toponomy, giving names and numbers to places and functions
- A clear, simple wayfinding system
Signage is a critical ‘wayshowing’ component of wayfinding. Information displayed in the signage needs to comply with the following:
- Be organised and presented in a logical, sequential layout
- Contain a maximum of five destinations in the case of directional signs
- Be listed at the top of the hierarchy or highlighted as primary information in the case of key hospital hub destinations
- Be presented lower in the information hierarchy in the case of secondary destinations
- Be grouped and ordered with logic relevant to the destinations listed in the case of destinations on signs, either in alphabetical order according to the direction to the destination in clockwise order or according to the order of the distance to the destination (closer destinations first)
- Connect labels (destinations) to arrows
- Arrow designs should be based on the ISO arrow (ISO 7001)
- Colour coding of floors or as a method of differentiating space may be used, however, people do not always perceive that the colour use has significance. This is worse for people who are colour blind. It is, however, a useful component of the wayfinding system
- Signage should use the following:
- Accessible terminology – common references that everybody understands
- Avoid the use of acronyms and use universally understood symbols
- Provide clear contrast between the information content and its surrounding environment
- A finish that does not detract or obscure the signs intention
FIGURE 4: DIRECTIONAL SIGNAGE
Mapping is an important part of wayfinding system. Maos should be located at strategic points throughout the site and allow visitors to orlantate themselves. The maps should be consistent with the signage and the typology needs to be clear.
Photograph 1: Mitchells Plain Hospital, Cape Town: Maps strategically placed per floor
2.13. In the inpatient facility
Appropriate signage for all the internal rooms and the external buildings should make use of universal signage and should, take the provincial policy on signage and wayfinding into account as far as possible. Comprehensive signposting shall be provided for all hospitals. Signposting will clearly identify staff, patient and visitor areas. It will also draw attention to restricted areas.
The patient information board should be supplied and fitted by the contractor.
2.17. Ventilation and air management
Adequate ventilation throughout the health facility is important as poor ventilation affects patients and staff, and puts them at risk of being infected with nosocomial diseases. It is therefore necessary to ensure that spaces are ventilated so that the quality of the air breathed is improved by diluting the air and removing pollutants that are harmful. The main aim is to provide ventilation that maintains thermal comfort and indoor air quality that reduces the risk of cross-infection. This can be achieved through natural, mechanical or hybrid methods of ventilation.
The chosen method will have a significant effect on the design of the inpatient unit.
2.18. Day- and night-time illumination
- All rooms should be provided with the required electrical illumination
- All patient beds should be provided with a reading light
- Night lights should be provided in passages so that they do not disturb patients
- Emergency lighting is critical in inpatient units such as paediatrics, theatres and ICU
2.19. Fire detection and alarms
Refer to Fire Regulations and SANS 10400 Regulations
- All inpatient units should have escape doors in case of fire
- The inpatient units should be provided with smoke detection systems
- Sprinkler systems are not recommended
- Fire extinguishers should be provided and slightly recessed so as not to cause obstruction
- All inpatient units should have an evacuation plan that is aligned with escape routes
2.20. Security
- Access to and from the inpatient unit
- Spaces that must be secured (medication store)
- Security in individual spaces of the unit
2.21. Supply and disposal
- Laboratory – collection of specimens
- Mobile X-rays
- Central stores – disposables, stationery, cleaning materials and new equipment
- Pharmacy – medicines and drugs, delivery of prescriptions and return of empty recyclable containers
- Central Sterile Services Department (CSSD) – sterile packs, return of opened unused packs and used recyclable equipment
- Linen store – clean linen, return of dirty linen
- Kitchen – patient meals (the size of the kitchen depends on the meal production and delivery processes involved)
- Central Cleaning Depot (CCD) – cleaning equipment
- Refuse – general waste (domestic), pathological waste for incineration, recyclable waste, sharps.
- To and from the laboratory – the collection of specimens
- Mobile X-ray equipment – space around patient beds and parking space for the equipment (a bay off the passage)
- From the central stores – delivery of disposables, stationery, cleaning materials and new equipment
- To and from the pharmacy – delivery of medicines and drugs, delivery of prescriptions and return of empty recyclable containers, sending of prescriptions to the pharmacy
- To and from the CSSD – delivery of sterile packs, return of opened unused packs and used recyclable equipment
- To and from the linen store – delivery of clean linen, sluicing of linen and return of dirty linen to the laundry
- To and from the kitchen – delivery of patient meals in a trolley, trolley parking in the inpatient unit and return of the utensils and cutlery in the trolley back to the main kitchen
- CCD – delivery and storage of cleaning equipment
- Refuse – removal of general waste (domestic), pathological waste for incineration, recyclable waste, sharps
- General hospital policies relevant to the various departments, such as linen supply and waste management, should be applied
2.22. Medication management
- Pharmacy staff should be consulted with regard to medication and intravenous fluids storage requirements for each inpatient unit.
- The inpatient unit depends on the pharmacy for pharmaceutical support. This includes inpatient unit medication, scheduled drugs, patient prescriptions and discharge medication. • Security and access control to medication rooms should comply with local legislative Government Gazette No 25872, Pharmacy Act, 2 January 2004 – jurisdiction requirements and the hospital policy.
- The location and design of the medication room should minimise travel distances, noise and disruption to staff undertaking medication-related activities in order to reduce error. All medication should be stored in a temperature-controlled, locked environment. The medicine trolley, inpatient unit stock and patient prescriptions should be stored in a medicine room that should be close to and directly visible from the nurses’ station.
- The management of intravenous fluids should be clarified for the specific facility as to the quantity to be stored within the clean utility room (inpatient unit bulk stock is kept in the surgical and medical storeroom with small quantities kept in the clean utility).
- If additives are introduced to intravenous fluids in the inpatient unit, it should occur in the clean utility room.
2.23. Options for dispencsing within the inpatient unit
Lockable medication trolleys should be stored in the medicine storeroom behind or directly opposite the nurses' station so that the store is in full view of nurses at all times.
Figure 6: relationship of medicine store
2.24. Equipment cleaning
Medical equipment: The operational narrative should guide whether reusable items will be processed in the inpatient unit or whether they will be sent to the CSSD
Beds: These are cleaned in the inpatient unit
2.25. Storage - equipment
The equipment store is intended for storage of equipment that has to be floor parked or stored on shelves and for equipment that may require the recharging batteries. The requirements will vary and need to be defined so that appropriate storage space is allocated according to the requirements of the inpatient unit and the needs of the patients and staff.
The equipment store should be located close to the sluice room, as equipment requires cleaning and disinfecting before storage.
Equipment should be organised so that it is easily accessible by staff when required. Items used regularly, such as an emergency trolley with oxygen cylinders, scales and mobile blood pressure (BP) units may be stored locally in equipment bays. Rarely used items may be stored in a central equipment store. A long rectangular room allows the optimum use of space.
Power outlets (4 to 16) should be provided for the recharging of equipment, depending on the equipment list compiled per level of care.
Equipment, particularly larger equipment that has to be floor parked, needs to be defined so that appropriate storage space may be allocated according to the needs of the patients and staff.
2.26. Storage – sterile supplies and consumables (sterile and surgical stores)
Supplies should be stored off the floor, with the lowest shelf at least 300 mm above floor level to avoid mechanical damage during cleaning, and the top shelf no higher than 1 850 mm.
Figure 7: Interactive relationship for the management and control of supplies and consumables
2.27. Storage of patients' belongings
The method of storing patients' belongings depends on hospital policy. However, the following considerations must be taken into account:
- Method of storing patients' belongings separately
- System where contaminated clothing can be washed and decontaminated prior to storing in a patient's kitroom
- Labelling method
- Security
- Type of storage, i.e. cupboards per bed unit, store per ward or central store for the whole hospital managed by a dedicated staff member who registers all items handed in
- Size of the facility: many patients coming from rural areas will carry numerous items (e.g.blankets) with them that need to be stored until they are discharged
2.28. Waste management
Operational policies for waste management and waste minimisation should be supported, particularly with regard to the following:
- Provision and location of dirty utility rooms so that staff do not have to traverse public and administration areas while transporting contaminated waste items
- Provision and location of recycling bins
- Location of sharps container
3. Inpatient unit acivities
Inpatient admissions to an inpatient unit need to provide for the following patient activities:
- Clinical diagnostic activities (medical, diagnostic imaging, laboratory, inpatient unit rounds, doctors' visits, going for operations, investigations or rehabilitation)
- Activities of daily living (dressing and undressing, eating, drinking, personal toilet and ablution activities)
- Social activities such as receiving visitors
- Patients might be disabled or might be semi-mobile due to weakness, age, or the disease profile
TABLE 4: INPATIENT UNIT ACTIVITIES
Category | Activity | |
---|---|---|
A | Patient | Patient Patient may be disabled and wheelchair bound
Patient to dress and undress in vicinity of the bed Patient to take meals in bed or at the bedside Patient to read, watch TV or use a computer Patient to receive treatment and medical care from therapeutic and clinical staff, either lying down or sitting up in bed or in a chair Patient to wash hands |
B | Nursing care | Teaching
Stripping and making beds Transfer patient from wheelchair or patient trolley manually or by means of a patient-lifting device Patient observation and clinical (doctor’s) rounds Transporting patient to theatre on his or her hospital bed Treatment procedures such as intravenous fluids, traction, etc. Emergency procedures, e.g. patient resuscitation Coordination of patient care, observation, writing up of clinical notes, entering data into computers, making and receiving phone calls and washing hands |
C | Medical intervention | Diagnostic procedures, such as mobile X-rays and ultrasounds, electrocardiograns (ECGs)
Teaching Treatment procedures such as intravenous fluids, traction, etc. Emergency procedures, e.g. patient resuscitation Examination of patients and washing hands Writing reports and instructions, writing up of clinical notes, entering data into computers Washing hands |
E | Rehabilitative intervention:
physiotherapists, social workers, occupational and speech therapists, paharmacist and radiographers |
Occupationally specific therapeutic interventions
Patient consulting Diagnostic procedures, such as mobile X-rays and ultrasounds, ECGs, etc Washing hands |
F | Clerical or administrative | Answering telephones, receiving patients and visitors to the patient unit
Writing reports and collecting and entering data and statistics, ordering food and other consumables Washing hands |
G | Ancillarystaff (aide, patient assistant) | Assisting patients in wheelchair
Entertaining patients Washing hands |
H | General staff | Serving food to patients
General tidying work Daily cleaning - sweeping, dusting, washing up Routine cleaning - floors, windows, walls Washing hands |
I | Maintenance staff | Maintenance- replace globes, fix fittings, reseal floors and repair work to maintain the inpatient unit
Washing hands |
J | Visitors | Visit patients and socialise in the inpatient unit or day room
Washing hands |
4. Client expectations
4.1. Patient expectations
- Patient privacy and dignity both in the design of the facility and in the treatment of the patient
- Personal safety and security of the patient’s own possessions
- The provision of patient comfort in the facility, e.g. a clean and uncluttered environment, an outside view, low noise levels in the facility, the availability of technical services (staff call system, reading light)
- Adequate availability and visibility of nursing staff
4.2. Staff expectations
- A work environment with reduced walking distances, but increased patient observation with minimum staff (optimal care)
- Improved patient risk management, e.g. availability of technical bed-head services, availability of clinical hand basins in patient and staff areas, the availability of automatic bedpan washers, improved environmental control (with reduced infection risk)
- A safe work environment, e.g. suitable height of shelves and service outlets, non-slip floors, view of unit entrance and exit, access control
- Personal safety and security of possessions, e.g. staff lockers, staffroom.
5. Location and inter-departmental relationships
The design of smaller hospitals may allow the inpatient units to be arranged over the same level. However, inpatient units of larger hospitals may be arranged into multistorey blocks separate from the diagnostic and treatment facilities. This makes it easier to place the inpatient unit block away from noisy areas, ensures patient privacy and safety, and avoids visitors, staff and service traffic through the inpatient units.
Stacking of the inpatient units in multilevel blocks also allows more consistent planning of inpatient accommodation.
The following inter-departmental relationships with the inpatient units are recommended:
- Patient administration and primary circulation should be central to the entrance with the access route to the inpatient facilities off the primary circulation route.
- The obstetric inpatient units should be close to the delivery suite and close to the operating theatre, preferably on the ground floor or with a direct lift access to theatres.
- In district hospitals, operating theatres, HCUs, orthopaedic inpatient units and surgical inpatient units should have a close relationship and preferably be on the same floor.
- Rehabilitation, physiotherapy and occupational therapy should be close to rehabilitation inpatient units and accessible to the outpatients department and the inpatient units.
- Hotel services (cleaning, linen and food services), mortuary services and maintenance units should have a reasonable relationship to the inpatient units. The mortuary, kitchen and laundry should have better access than all other services, especially at night (particularly mortuary services).
- Visitors to the inpatient units should not cross functional access with the services to and from the inpatient units.
5.1. Staff overnight facilities
figure 8: hospital model of care
Figure 8 illustrates the position of the inpatient units in relation to the hospital support services and the outpatient services. Inpatient units should be located separately, away from the mainstream, in the hospital complex to enable better privacy and separate the flow path of inpatients from outpatients after entering the main entrance to the hospital. This reduces the volume of traffic in the main passage to the inpatient units and avoids visitors, staff and service traffic through the inpatient units.
- District hospital
- Surgical inpatients are the inpatients most closely associated with the theatres.
- Regional hospital
- Orthopaedic inpatients are the inpatients most closely associated with the theatres.
- Tertiary hospital
- Subspecialist inpatients, such as neurosurgery and cardiology, are the inpatients most closely associated with the theatres.
Figure 9: departmental relationships
6. Flow patterns
Point of entry
- Patients or visitors will access the facility through a secure entrance to a parking area or drop-off point from where there should be a clear direction (signage) to the required point of entry.
- Alternatively, a patient will arrive via emergency services to the emergency unit or the maternity services entrance
- Staff members access the facility through a secure staff entrance from a staff parking area or drop-off point.
The diagram above illustrates three main inpatientstreams that will accommodate acute admissions, maternity admissions and planned admissions. To ensure resource efficiency, the workflow and zoning should support these inpatient streams.
The following flow paths relate to community, inpatients, clinical, visitors and support services to the inpatient units.
Figure 12 : patient-flow diagram
The workflow between departments has an impact on patient ans staff movement, as well as goods and service deliveries to the wards. Minimum walking distances between departments should be planned in the interest of resource management and traffic reduction through the facility
Figure 13: clinical flow diagram
The diagram above indicates the clinical workflow dependencies between the clinical service and departments.
Figure 14 : visitors flow diagram
Figure 14 indicates the routes that visitors to the inpatient units would follow and Figure 15 shows the access routes for the service departments that would ensure access to the inpatient unit without affecting traffic through patient or clinical areas.
Figure 15:L Support services workflow diagram
Separation of clean and dirty flow paths in the inpatient unit
Upon arrival arrival at an inpatient unit, a single entry point is preferred in order to control traffic in and out of the inpatient unit. However, infection control principles dictate that clean services should enter at a separate point to where waste and contaminated goods are taken out of the inpatient unit.
Figure 16: Entrance to and from the inpatient unit
Patients, visitors and clinical staff, along with clean goods and services (including food deliveries), should enter and exit through the main entrance. Soiled and contaminated goods should exit from the inpatient unit through a separate entrance, preferably positioned at the most distant point from the main entrance. It must be noted that an exit separate to the main entrance is required in terms of fire regulations. This exit may be utilised to take out the contaminated goods.
It is important that deliveries to and from the inpatient unit are managed in such a way that they do not clash with visitors arriving and leaving. Goods and services should be delivered at times other than visiting hours.
7. Functional zones
The inpatient unit functions as a stand-alone unit consisting of six separate functions
Table 5: inpatient unit functional zones
Zone | Accommodation spaces |
---|---|
Administration spaces | Inpatient unit management, nurses' station and other office spaces as required |
Public spaces | Entrances, circulation and waiting areas |
Patient spaces | Patient accommodation and ablution facilities, patient day rooms, disabled showers, treatment room. |
Service and support areas | Inpatient unit kitchen and storage, clean utility, sluice, stores, cleaners' room, linen, cleaning, medicine store, dirty utility and waste management |
Staff spaces | Staffroom, locker area, ablutions, overnight accommodation* |
Teaching spaces | Training or meeting room( in district hospital staffrooms could be used) |
These zones create the therapeutic environment required for successful healthcare delivery at inpatient nit level.
Figure 17: adult inpatient accommodation: internal zoning and relationships
Functional relationships within the inpatient unit
Inpatient unit layouts will vary depending on individual needs per project as outlined in the health and design briefs. However, general principles of design apply and the location of facilities within the inpatient unit should be a logical process optimising the workflow and travel distances for staff from service and storage areas to the patient’s bedside.
The following general principles apply to functional relationships within the inpatient unit:
- The visitors’ waiting room and visitors’ toilet should be outside the entrance to the inpatient unit and may be shared by two inpatient units on the same floor.
- One central entrance to the inpatient unit with access control is preferred.
- The kitchen should be close to the main entrance of the inpatient unit.
- Deliveries and removal of kitchen trolleys should be managed so as not to clash with visiting hours and inpatient unit rounds.
- Nurses’ stations should be positioned centrally with direct visual access to the inpatient unit entrance and in close proximity to the single-bed inpatient units, where the most critical patients would be accommodated.
- The larger bed units for less critical patients could be positioned further away from direct nursing supervision.
- The single-bed units, clean utility, medicine store and treatment room should be positioned near the nurses’ station.
- Areas such as the inpatient unit kitchen and staff areas could be positioned off the main centre of the inpatient unit.
- The clean linen store (or trolley) and sluice room should be close to the bed units to reduce walking distances for the nursing staff.
- Dirty utility rooms should be positioned close to the separate exit door to facilitate collection of the contaminated items and waste, avoiding cross-contamination with clean goods by separating the workflow of clean and dirty paths in the inpatient units.
- Design should minimise the distance between patient bed units, staff workstations and support rooms to facilitate the efficient delivery of patient care and optimal staff utilisation.
- Each bed unit will be serviced by staff and support facilities, therefore access to supplies and means of disposal is essential. One of the primary goals is to minimise the distance between patient units and workstations and support rooms. The inpatient unit should be planned to provide a public/clinical and a utility/service division.
- The unit manager’s office should be positioned for maximum supervision of both clinical and household functions (close to the entrance).
- The clinical administration area and doctor’s office should be near the nurses’ station with access to the clinical spaces.
- The sluice, linen, and storerooms should be positioned central to the patient bed units to reduce walking distances for the nursing and cleaning staff.
8.1. Ablution facilities
Patient ablution facilities should be en suite directly accessible from the adjacent bed unit. Ablution facilities for clinical staff may be provided in association, but not combined with staffroom areas. Designated toilets for clinical staff should be provided.
8.2. Key room relationships
It is important that key room relationships are maintained such as illustrated in figure 18.
Figure 18: Room relationships that promote the principal of 'clean to dirty' flow
Figure 19: Room relationships with the inpatient unit (Example 1)
Figure 20: Room relationships with inpatient unit (Example 2)
9. List of rooms
The majority of rooms in ward are standard rooms that may be found in other departments in the health facility. These rooms have been detailed separately in the IUSS: GNS generic room requirement sheets. These sheets must be referred to when planning the rooms.
Table 5 lists the rooms found in the inpatient unit and indicates the rooms that are standard and those that are non-standard. The non-standard rooms that are described in more detail under 'room requirements'. The standard rooms are described in less detail as they are detailed in the IUSS: GNS generic room requirement sheets.
Table 6: Loss of rooms: Standard and Non-standard
Room | Standard | Non-standard |
---|---|---|
Patient areas | ||
Bed unit - Standard patient area: | ||
Single-bed unit | x | |
Two-bed unit | x | |
Four-bed unit | x | |
Patient day room(provided in a district hospital) may be shared between wards | x | |
Patient ablutions: | ||
En suite facility with shower, toilet and hand basin (all should be disability friendly) | x | |
Assisted bath where required | x | |
Assisted shower | x | |
Staff areas | ||
Office - manager | x | |
Office - Counselling or doctor (optional) | x | |
Nurses' station | x | |
Clinical admin area | x | |
Office - administration | x | |
Staffroom | x | |
Staff lockers can be provided in a passage off the main passage leading to the restroom | x | |
Toilet - staff (male and female) | x | |
Service support areas | ||
Bay - mobile equipment | x | |
Bay - Resuscitation trolley | x | |
Clean utility ( setting out the sterile packs and treatments) | x | |
Cleaners ' station | x | |
Dirty utility (refuse and dirty linen) | x | |
IT room - consult with information and communication technology (ICT) planners depending on the hospital | x | |
Sluice room | x | |
Store - Clean linen | x | |
Store - Equipment | x | |
Store - Kit (patients' clothes and belongings could be in a central area or per inpatient unit - refer to brief) | x | |
Store - Medicine | x | |
Store - Consumables (surgical and medical) | x | |
Treatment room | x | |
Inpatient kitchen | x | |
Body-holding room | x | |
Public areas | ||
Inpatient unit corridor | x | |
Entrance | x | |
Visitors' waiting area | x |
10. Room requirements
10.1. Bed unit – standard patient area
These guidelines allow space in all bed units for equipment and the activities around each bed and between beds.
10.2. Location and relationship
En suite bathrooms shall be dedicated to each room and will be directly accessible from the bed unit.
Figure 21: Left-right orientation of a patient bed
Important: The reference to the left and right side of the bed should describe the patient's left and right when lying down in the bed facing the ceiling. The bedside locker is placed according to the patient's preference.
Staff capacity
Space is required to adequately accommodate the activities taking place at the patient's bedside and the movement by staff around the bed, which can involve several staff at any one time and may also include the use of equipment at the patient's bedside.
These activities can involve the following:
- Doing clinical observations taking blood, blood pressure and the patient’s temperature
- Assisting with activities of daily living: dressing, feeding and washing
- Treatment procedures, such as intravenous fluids, traction, etc.
- Examining the patient
- Stripping and making beds
- Transferring the patient from a wheelchair or patient trolley manually or by means of a patient-lifting device (patient may arrive in a wheelchair or on a patient trolley)
- Patient observation and clinical (doctor’s) rounds
- Diagnostic procedures, such as X-rays, ultrasounds, ECGs, etc.
- Transporting the patient to the theatre on his or her hospital bed
- Emergency procedures, e.g. patient resuscitation
- Recording of notes at the bedside either manually or on the computer (clinical staff)
- Cleaning and dusting around the bed (clinical staff)
- Maintenance work (maintenance staff)
10.4. Patient activity
- May sit next to the bed
- Receives treatment from therapeutic and clinical staff while lying down or sitting in bed
- Receives visitors
10.5. General requirements
The following is required in the bed unit space:
- Space should be provided for a bed and bedside locker next to each bed, preferably on the right.
- Temperature in bed units should be between 20 ˚C to 23 ˚C.
- Positive air pressure should be maintained in bed units.
- Bed curtain rails and curtains should be provided for privacy around each bed.
- Each bed unit should have a disability-friendly en suite shower, toilet and hand basin with a call button for the nurse.
- A clinical hand basin with elbow taps, goose neck and an outlet must be provided in the bed unit. The basin and backsplash should be a moulded unit. A wall-mounted mirror, soap dispenser and paper towel dispenser should be provided with each hand basin.
- Waste bins should be next to but lower than the hand basin. There should be one for medical waste, one for sharps (refer to brief document) and one for general waste.
- There should be adequate lighting provision (natural and artificial light) – daylight is important in the bed unit.
- The patient should have visual privacy without compromising staff control and observation of the patient.
- A standard equipment list per level of care (district, regional or tertiary) should be made available. The list will distinguish between loose equipment to be provided by the client and fixed (mounted) equipment to be provided and installed by the contractor.
10.6. Space requirements
Ergonomic studies have established that most activities carried out at the bedside can be accommodated within the dimensions 3 450 mm (width) × 4 100 mm (depth). This represents the clear bed space and does not include space for fixed storage.
One bed unit equals a minimum of two and maximum of four beds per 32-bed inpatient unit in a district or regional hospital. The clinical brief will outline the tertiary hospital requirements.
It is preferable for beds on opposite sides of the room to be offset to provide greater privacy.
Single-bed unit approximately 15 m² minimumFour-bed unit approximately 44 m² (majority of rooms) minimum
Six-bed unit approximately 65 m² minimum
Drawing 1: single-bed unit(minimum space dimension requirement)
DRAWING 2: TWO-BED UNIT (A) (MINIMUM SPACE DIMENSION REQUIREMENT)
10.7. Bed services
TABLE 7: BED-HEAD SERVICES PER LEVEL OF CARE
10.8. En suite sanitary facilities
Description and function
Location and relationships
- Nurse call button connected to the nurses’ station
- An adjustable overhead hand shower head with flexible hose
General requirements
- Doors must open outwards from the en suite bathroom and must be fitted with an emergency release function.
- The shower must have a shower curtain
- The seat must fold up in the shower area and there should be a bench outside the shower (but within the en suite bathroom) for personal belongings. Three durable clothes hooks are to be mounted on the wall above this bench.
- Fittings must be mounted in such a way that the water temperature can be adjusted without the patient or nurse getting wet.
- The exit door must be fitted with escape hardware to allow staff access in the case of an emergency.
- Nurse call and emergency call buttons and indicators should be provided that are tamperproof.
- Epoxy grout is to be applied in all tiled areas.
- Fittings, including grab rails, are to be installed to the toilet and shower area, including towel rails.
10.9. Assisted shower
Description and function
Location and relationships
- Be located away from bed units, but within close proximity to the nurses’ station to enable staff supervision and observation
- Have direct access off the main inpatient unit passage
Activities
- Patients should be able to receive visitors
Services
General requirements
- Day rooms to be located inside the inpatient unit without outside access, or it may have outside access (to the garden or a balcony). This depends on the inpatient unit type and the need for security.
10.12. Treatment room
Description and function
Location and relationships
Activities
- Access to patients from both sides of the couch
- As the patient may be ambulant, in a wheelchair, on a trolley or in a bed, patient transfer may be required to the examination couch
- Private examination and discussion with the patient
- Specimen collection (e.g. bone marrow)
- Wound treatment (applying or renewing dressings)
- Other examinations and treatment activities specific to the medical discipline
- Treatment by a physiotherapist or occupational therapist
- Completing special examination requests and writing reports
Services
- Four electrical points
- A vacuum
- Data and telephone terminals
- A stainless steel sink
- A good-quality examination light, preferably mounted on the ceiling
- Bed-head service with two power outlets on the right of the patient examination couch and three power outlets on the left, oxygen and vacuum outlets, and an equipment rail for mounting items such as a suction unit, oxygen flow meter and nurse call button
- A wall-mounted X-ray viewing panel where applicable
General requirements
- A door that is wide enough for a bed to pass through
- Curtains for patient privacy
- A stainless steel worktop with a cupboard underneath it for stock (± 1.0 m)
- Positive pressure
- Temperature in the treatment room maintained at between 20 °C and 23 °C Equipment
- A double-step foot stool
- A mobile drip stand
- A wall-mounted diagnostic set
- A mobile vital signs monitor (nibp+hr+sao2);
- An emergency oxygen cylinder on a mobile stand
- An ECG machine on a mobile trolley
- A fitted desk unit with a chair
- A pedal bin or kickabout with a bucket
- Viewing of the patient by the family
Services
- Cupboards for storing equipment
Considerations
- Décor to create a calm atmosphere
- Pastel, gentle colours to be used on walls and in curtains and blinds
- The room may be shared by two wards Equipment
11.2. Clean utility
Description and function
Location and relationships
Activities
- Storage of sterile packs from the CSSD
- Storage of liquids from the pharmacy
- Hand washing by staff prior to trolley preparation for bedside treatment or procedures
- Preparation of trolleys for treatment or procedures in the procedure room
- Warming of solutions required during treatments or procedures Services
- One double 15 Amp plug above counter height
- Standard power outlet for liquid warmer: stand-alone or standing on the worktop General requirements
- Lockable cupboard with shelving for sterile packs and storage of vacolitre
- Stainless steel worktop: space for one 600 x 450 mm instrument trolley and two 450 x 450 mm instrument trolleys underneath the worktop Equipment
- Liquid warmer: stand-alone or standing on the worktop
- Hand-washing by staff before leaving the room
- Report writing
- Water collecting and emptying cleaning buckets
- Hanging wet mops and cloths to dry
Services
- A drip sink with a hinged bucket grid for cleaning mops (not a slop-hopper) General requirements
Description and function
Location and relationships
Activities
- Writing reports
- Accessing and printing data from a computer
- Recording patient information in patient files and filing printed reports
- Digital radiology screens
- Case discussion and peer support
Services
11.5. Dirty utility
Description and function
Location and relationships Activities
- A microwave oven
- Four power outlets for the hot-water supply unit, 120 ℓ fridge/freezer combination and microwave, plus one extra point
- Continuous hot-water supply (hydro boil) unit placed over the sink drainage
- A stainless steel hand basin with a paper towel holder and soap dispenser
- A double-bowl sink with drip trays
- Cupboards for keeping detergents, cups, saucers and glasses General requirements
- Suitable workspace and floor covering is needed that is easy to maintain
Equipment
- 120 ℓ fridge/freezer combination
- Microwave oven
- Tea trolley
- Food trolley (from main kitchen)
Services
- Data cabling to specialist approval and design
- Power points to be specified by the IT specialist
- Access control may be required
General requirements
- The planning of this room must be coordinated with the IT consultants and the clinical staff.
11.8. Nurses’ station
Description and function
The nurses’ station is the administrative base and communication centre for the inpatient unit and the enquiry point for patients and visitors. It provides a focal point to which all staff, whose time is mostly spent with patients, can return to record data, issue and receive information and receive verbal and written instructions. It provides for the coordination of patient care, observation, writing up of clinical notes, entering data into computers, and making and receiving phone calls. The station must accommodate nurses, an inpatient unit clerk, and, at times, doctors.
The area controls the movement of patients, staff and visitors entering and leaving the unit and can receive mail, flowers and a variety of other items that may be delivered to the unit. The inpatient unit clerk or receptionist is generally located in this area with ready access to files and stationery. One nurses’ station in an inpatient unit, central to the bed units, will allow for the observation of the main patient areas and, where possible, people entering and exiting the inpatient unit
Decentralised nurses’ stations may be considered for immediate work associated with patient care: the review of patient notes, files and tests (short work). This is facilitated by the use of electronic record systems and point-of-care management. The floor area of the nurses’ station will vary according to the activities and services required.
Activities
- Access to the electronic patient system
- Making and receiving phone calls
- Writing reports
- Updating the patient bed allocation board
- Accessing and printing data from a computer
- Recording patient information in the patient’s file and filing printed reports
- Controlling the nurses’ call system
- Monitoring service alarms (e.g. fire alarm system)
- Managing the key cupboard
- Managing digital radiology information
- Providing a contact point for doctors and nurses
Services
- Two data points
- Six power outlets (for two computers and screens, a fax machine and printer)
- Hands-free clinical hand basin, elbow taps, a mirror, paper towel holder, soap dispenser and wall-mounted waste paper bin
- Nurse call system connected to a display panel at the nurses’ workstation or mounted on the wall directly behind the nurses’ station
- Fire alarm/smoke detection panel mounted on the wall directly behind the nurses’ station
- Alarm panel for gas and water mounted on the wall directly behind the nurses’ station
- Power outlet for digital X-ray monitor and keyboard
- Access control (inpatient unit entrance and exit plus dirty utility outside door)
- Emergency power and uninterrupted power supply (UPS)
- Access control panels at the inpatient unit’s entrance and exit, including the outside door of the dirty utility
- Medical gas shut-off valves in visual control and within easy reach of the nursing staff General requirements
- Large workstation with a view of the entrance, and optimal observation of the most acute patients
- Suitable workspace for the inpatient unit clerk (should no separate office be provided) and the nurses to work at the station with space for two computers, two telephones and a printer
- Work surface and space for filing, shelves to accommodate files and stationery with drawers and cupboards, i.e. 20 lever-arch files (for policy documents, etc.) in a cabinet, ten lever-arch files in cupboards below the work station, plus space for 30 different types of forms (all A4) in pigeon holes above the work station
- All surfaces must be impervious and designed for easy cleaning
- Access to pneumatic system for laboratory samples (regional hospitals – dependent on the hospital size; tertiary hospitals as standard)
- Air conditioning : ± 22 °C
- Space for a dictionary and reference books
- A key cupboard mounted on the wall behind the nurses’ station
- Space to store and recharge haemoglobin and glucose meters
- Space to store and recharge diagnostic sets
- Space for the patient allocation board
- Space for an adult scale with length meter
- Space for an emergency trolley
- Space for an oxygen cylinder on a mobile stand
- Space for three observation trolleys or mobile non-invasive blood pressure (NIBP) machines • Wall-mounted wipe board and pin-board
Fittings
- Counter, with sitting space for at least four people
- Above- and under-worktop storage space for policy manuals, registers and report documentation
- Access to medical gas shut-off valves must be in visual control and within easy reach of the nursing staff
- Space for two telephones, two computers and a printer, the nurse call panel, fire alarm and smoke detection panel, and medical gas and vacuum supply.
Equipment
11.9. Patient kitroom
Description and function
The provision of a kitroom could require a central or unit kitroom. The recommended minimum unit size of 6 to 8 m² is suggested. The room is used for the safe storage of patients’ clothes and belongings, excluding valuables and money.
Location and relationships
- Urine testing and temporary storage of laboratory samples
- Washing and temporary storage of medical instruments
- Safe usage, service and maintenance of automatic bedpan washer
- Hand washing by staff upon entering and before leaving the room
Services
- A stainless steel clinical hand basin with elbow taps and a gooseneck outlet with tiles above it, soap dispenser and paper towel dispenser
- A double deep-bowl stainless steel sluice sink unit with elbow taps and a gooseneck outlet, as well as a hand-held shower on a flexible hose
- An automatic bedpan washer and power outlet at 1100 AFFL (ensure that the choice of the type of bed pan washer is made early in the design phase to enable adequate provision for drainage)
- A single stainless steel sink with workspace for washing medical instruments
PHOTOGRAPH 4: EXAMPLES OF SLUICE ROOM EQUIPMENT
*- Counting linen
- Unpacking received linen (mostly in canvas bags)
- Loading clean linen onto the linen trolley General requirements
- Lockable door (undercut door for ventilation)
- Perforated or slated shelving Need to make provision for supplies over weekends and private holidays in rural areas
Equipment
PHOTOGRAPH 5: EXAMPLES OF LINEN TROLLEYS AND LINEN STORAGE
11.12. Store for consumables
Description and function
Safe storage should be provided for the storage of clinical consumable items, like intravenous fluids and sets, syringes, needles, bandages, etc. Provision should be made for a minimum size of 9 m² per 28- to 32-bed inpatient unit. Allow 0.183 m² stock area per patient.
Location and relationships
The consumables store should be centrally located close to the clean utility and have direct access to the inpatient unit.
11.13. Equipment store
Description and function
The equipment store is used for the safe storage of medical equipment, traction accessories, the parking of mobile IV poles, wheelchairs, lifting poles, bed cradles and commode chairs. Plugs and shelves are available for recharging and storing electrical equipment. A minimum size of 12 to 20 m² is recommended. This will vary in larger hospitals with 400 or more beds.
Location and relationships
- Shelving
- Storage space for the medicine trolley used during the inpatient unit rounds
Equipment
- Medicine trolley
- Refrigerator with a thermometer and power outlet
Description and function
The staffroom is used by the staff for respite and relaxation during tea and meal breaks, especially where it is difficult for staff to use centrally located facilities at night. It may also be used for staff meetings and tutorials. It has facilities for preparing and/or heating refreshments, snacks and meals, washing utensils and disposing of food waste.
A minimum area of 15 m² is required. Size depends on the number of staff members using the facility and the usage of the facility. Allow 1.5 m² per person, assuming that a maximum of 40% of the inpatient unit staff will utilise the room at any one time.
Location and relationships
The staff restroom could be shared between two inpatient units, or one space could be provided per floor.
Activities
12.3. Staff toilet
Description and function
This is a room containing a toilet and hand basin for staff use. A minimum of 3 m² is recommended. (No urinals should be installed.)
Location and relationships
Description
Location
Services
- One data point per bedroom
- One double plug for computers
- One power outlet adjacent to the bed for a bedside lamp
- Toilet, shower and hand basin in shared ablution area
General requirements
- Three electrical points and data point
- Telephone point
General requirements
- Desk and two chairs
- Filing cabinet
- Stationery cupboard
- Pinboard
- Lockable office
Services
General requirements
- Natural light is desirable
- Waiting areas may be shared between inpatient units
- A play area for children
- General and disabled-friendly ablutions
Equipment and furniture
PART C - ENGINEERING CONSIDERATIONS
- Service panels enclosing oxygen, suction and air outlets
- Ventilation
- Fire detection and alarm systems
- Resilience of electrical supplies
- Lighting systems
- •
PART D - STANDARD COMPONENTS
LIST OF ROOMS
LIST OF ABBREVIATIONS
ACDP | Advisory Committee on Dangerous Pathogens |
ACH | Air changes per hour |
AHIA | Australian Health Insurance Association |
AII | Airborne infection isolation |